TM-1104 AC/DC

TM-1104  700A AC/DC Transducer

 
 
 

Application

  • Before start the test, take all precautionary measures for operator’s safety (electrical protection gloves, etc.)
  • Even if it is possible to insert / remove energized conductors from the jaws (symbol  ), de-energise (if possible) the conductors under test
  • Connect clamp’s output terminal to the inputs of the instrument to be used as indicator
  • Select the 700A desired range on clamp. The yellow LED “ON” should be on. Verify that “Low Bat” red LED it’s off. If no, open the back battery cover and replace the batteries. 
  • Verify the zero at display of instrument to be used as indicator. If no, press ZERO key on clamp before start measurement
  • Open the clamp and put the tested conductor in the center of the clamp jaws. No gap is allowed between the connections of clamp jaws. Always consider the correct connection of clamp 
  • Read the current value in the indicator’s display
 
 
 
 

Features

  • AC Current
  • DC Current

 

 
 

Specifications

  • Safety:IEC/EN61010-1
  • Pollution degree:2
  • Operating Temperature/Humidity:-10 ~ +50 °C
  • Storage Temperature/Humidity: -10 ~ +60 °C
  • Overvoltage Catagory:CAT III 600V
  • Max diameter of cable:30mm
  • Dimension: 175mm(L)x70mm(W)x35mm(H).
  • Weight:about 200g. (Including battery)
TECHNICAL Specifications
AC Current
Current Range
Output Rang
Accuracy
(45~64Hz)
Overload
Protection
700A
1mV/1A
±(2.0% Reading+5A)
800Arms
(60second)

DC Current
Current Range
Resolution
Accuracy
40Hz~65Hz
Overload Protection
700A
1mV/1A
±(2.0%Reading+5A)
800Vrms
(60second)

 

 

Accessories

 

Download

File type
file name
Format
Download
TM-1104
EN. User’s Manual